Bushing Boots & Reusable Insulating Boots
Elastomeric boots that fit over switchgear bushings to insulate the cable-connector interface, available in a single-use bushing boot and a reusable insulating-boot design.
- ANSI C37.20.2
More datasheets
Full dimensional specifications and technical data, ready to download.
Choose a size
Selection Charts
| Product code | Total length | ID - bushing entry | ID - cable entry | Thickness |
|---|---|---|---|---|
| GSBB - 1 | 230 mm (min.) | 50.5 mm (min.) | 17.5 mm (min.) | 2.5 mm (min.) |
| GSBB - 2 | 230 mm (min.) | 50.5 mm (min.) | 22.0 mm (min.) | 2.5 mm (min.) |
Source: GALA BUSHINGBOOT and Reusable Insulating Boot catalogue sheet, Issue 2, January 2024.
Reusable insulating boot (GRRB) selection chart
| Product code | ID - bushing entry(min.) | ID - cable entry(min.) | L1(min.) | L2(min.) |
|---|---|---|---|---|
| GRRB - 1 | 44.0 mm | 20.0 mm | 175.0 mm | 170.0 mm |
Source: GALA BUSHINGBOOT and Reusable Insulating Boot catalogue sheet, Issue 2, January 2024.
Dimensions & Drawings
Bushing Boots are non-tracking elastomeric insulating boots used with terminations, fitting over switchgear bushings to insulate right-angled or straight connections up to 25 kV and protect against flashover or induced surges in switchgear and transformer boxes.
Reusable Insulating Boots suit PILC and XLPE cable terminations, giving the flexibility and dielectric strength needed between phase and phase and phase and ground, and are designed for disconnection and reuse — sealing the cable, cable lug and bushing against rodent ingress and high humidity.
Covered on this page
- BUSHING BOOTS
- REUSABLE INSULATING BOOTS
Features & Benefits
- Non-tracking elastomeric material enhances phase-to-phase and phase-to-earth insulation
- Protects against flashover and surges induced in switchgear and transformer boxes
- Reusable insulating-boot variant is designed for disconnection and re-use
- Provides complete sealing of the cable, cable lug and bushing
- Easy to install
Applications
- Insulating right-angled and straight bushing connections on switchgear up to 25 kV
- Terminations on PILC and XLPE cables
- Sealing the cable, cable lug and bushing against rodent ingress and high humidity
Standards & Compliance
- ANSI C37.20.2
FAQs
Frequently Asked Questions
What is the Bushing Boots & Reusable Insulating Boots used for?
It is used for:
- Insulating right-angled and straight bushing connections on switchgear up to 25 kV
- Terminations on PILC and XLPE cables
- Sealing the cable, cable lug and bushing against rodent ingress and high humidity
How do I choose the right size?
Use the selection chart on this page: it lists every code with its dimensions. If you are not sure which fits, send the dimensions you are working to with the form below.
Which standards and test methods are quoted for it?
These:
- ANSI C37.20.2
Where can I download the datasheet?
From the "Download datasheet" button at the top of this page, or here:
Can I get a quote, a sample or a size that is not listed?
Send your cable details, quantity and application with the "Request a Quote or Sample" form at the foot of this page. For a size or variant that is not in the chart, describe what you need there, or use Technical support at the top of the page, and the technical team will confirm what can be supplied.

47+
Years manufacturing

100+
Countries served

140
Products in range

ISO 9001:2015
Certified & tested