Manufacturing since 1979 · Exporting to 100+ countries

Send us your query

Fields marked with an asterisk are required.

Your enquiry details

Your local time. Leave both blank for any time.

Anti-Tracking Tube

Heat Shrink Non-Tracking Tube is used in medium-voltage cable joints and terminations up to 36 kV, produced from non-tracking cross-linked polyolefin material for exceptional insulation and long-term service reliability.

Choose a size

Selection Charts

D min.
Minimum internal diameter as supplied
d max.
Maximum internal diameter after free recovery
T
Recovered wall thickness (±10 %)
GAT non-tracking tube selection chart — all dimensions in mm
CodeD min.(mm)d max.(mm)T ±10%(mm)Spool length(m)
GAT 25/82582.230
GAT 35/1235122.430
GAT 45/1645162.530
GAT 55/2055202.530
GAT 65/2565252.515
GAT 75/2875282.515
GAT 100/38100382.515
GAT 120/45120452.515

Source: GALA INSULTUBE Non Tracking Tube catalogue sheet, Issue 2, January 2024.

GAT(HW) heavy wall selection chart
GAT(HW) heavy wall selection chart — all dimensions in mm
CodeD min.(mm)d max.(mm)T ±10%(mm)Length max.(m)
GAT(HW) 25/825851.5
GAT(HW) 35/12351251.5
GAT(HW) 55/18551851.5
GAT(HW) 65/25652551.5
GAT(HW) 85/30853051.5
GAT(HW) 100/381003851.5
GAT(HW) 120/451204551.5
GAT(HW) 140/501405051.5

Source: GALA INSULTUBE Non Tracking Tube catalogue sheet, Issue 2, January 2024.

Material properties

Technical Specification

Technical specification
PropertiesValueStandard
Physical
Tensile Strength10 N/mm² (Mpa) (min.)ASTM D638
Ultimate Elongation350 % (min)ASTM D638
Longitudinal Change-10 % (max.)ASTM D2671
Hardness45 ±10 Shore DASTM D2240
Water absorption0.5 % (max.)ASTM D570
Thermal
Accelerated ageing(120 °C for 500 hrs)ASTM D2671
Tensile Strength8 N/mm² (Mpa) (min.)ASTM D638
Ultimate Elongation250 % (min.)ASTM D638
Low Temperature Flexibility (-40 °C for 4 hrs.)No CrackingASTM D2671
Heat Shock (250 °C for 30 min.)No cracking or flowingESI 09-11
Shrink Temperature125 °CIEC 216
Continuous Temperature Limit-40 to +100 °CIEC 216
Electrical
Dielectric Strength15 kV/mm.(min)ASTM D149
Dielectric constant5 (max.)ASTM D150
Resistant to track & erosionNo Tracking, erosion or flame failure upto 3.25 kV for 20 min.ASTM D2303

Source: GALA INSULTUBE Non Tracking Tube catalogue sheet, Issue 2, January 2024.

A non-tracking cross-linked polyolefin tube for insulating medium-voltage cable joints and terminations up to 36 kV.

Covered on this page

  • Heat Shrinkable Tubes/Heat Shrink Sleeves
  • Anti-Tracking Tubes

Features & Benefits

  • Anti-tracking performance and erosion resistance
  • Halogen free, flame retardant
  • Good weather/UV resistance
  • High resistance to chemical, solvent, corrosion and fungus
  • GAT series (normal wall) and GAT (HW) heavy-wall selection charts

Applications

  • Insulation in medium voltage cable joints and terminations up to 36 kV

FAQs

Frequently Asked Questions

What is the Anti-Tracking Tube used for?

It is used for:

  • Insulation in medium voltage cable joints and terminations up to 36 kV
How do I choose the right size?

Use the selection chart on this page: it lists every code with its dimensions, and the key above it says what each column means. If you are not sure which fits, send the dimensions you are working to with the form below.

Where can I download the datasheet?

From the "Download datasheet" button at the top of this page, or here:

GALA-Non-Tracking-Tube-GAT-2024.pdf

Can I get a quote, a sample or a size that is not listed?

Send your cable details, quantity and application with the "Request a Quote or Sample" form at the foot of this page. For a size or variant that is not in the chart, describe what you need there, or use Technical support at the top of the page, and the technical team will confirm what can be supplied.

  • 47+

    Years manufacturing

  • 100+

    Countries served

  • 140

    Products in range

  • ISO 9001:2015

    Certified & tested

Need Anti-Tracking Tube for a live project?

Send us your requirement, call the plant directly, or take the datasheet with you.

Request a Quote or Sample

Tell us what you need — our technical team will get back to you.

Fields marked with an asterisk are required.

Your enquiry details